Transformer Selection Guide

The transformer’s primary voltage must be compatible with the boiler power voltage. Transformer sec-ondary voltage must be 120 VAC (220 VAC for export).

To select transformer size find the sum of all component VA requirement, i.e. ES-72 with ES38083V condensate return system and ES81600 automatic blowdown system requires:

Basic Boiler                        1/4 VA
ES 38083V                         3/4 VA
ES 81600                           1/2 VA
Transformer VA Required  1 1/2 KVA
 
Basic Boiler Transformer Size(kVA)
SSB, ES 12-72
ES 85-180
1/4
1/2
SVS 150-180
SVS 494-630
SVS 720-1620
1/2
3/4
1

*Refer to following table to compensate for additional loading due to specific options

Option Additional (kVA) Required
Water Feeds
ES99117, SSB99117
SV99117

-
1/4
ES38002, SSB38002A 1/4
ES38020A 1
SVS38020, SVS38021 1 1/2
Automatic Blowdown System
ES81600
1/4
Condensate Return Systems,
1PH
ES38083V, SVS38013,
SVS38014, SVS38015,
SVS38017


3/4
SVS38018, ES38084V,
SVS38022
1 1/2
SVS 38019 1 1/2
All 3-Phase Condensate Return
Systems†
1/4

† 3 pole motor starter required